120V, 220/240V, 50/60 Hz Voltage Disturbance Recorders
PowerWatch is the easiest way to monitor and record essential voltage disturbance information from any 120 volt North American or 220/240 volt Australian, European or UK power receptacle. Just setup your pre-determined disturbance threshold values or use the industry standard default values and plug it in. No wiring or dangerous connections required.

PRODUCT SPECIFICATION FOR 120V

Memory Size - 4,000 events.
Common Specifications - See page 30.
Software Specifications - See page 39.
Surge, Sag & Outage - Hot to Neutral Neutral to Ground
Range -  0 to 200 V rms 3 to 200 V rms
Accuracy -  +/-1 V rms +/-1 V rms
+ resolution + resolution
Resolution –  1 V rms 1 V rms
Impulse - Hot to Neutral Neutral to Ground
Range –  100 to 2500 V peak 50 to 2500 V peak
Accuracy -  +/-10% of reading +/-10% of reading + resolution + resolution
Resolution -  10 V 10 V
Hot to Neutral Neutral to Ground
Width Detection: 1 µsec minimum 1 µsec minimum
Phase Angle - 
Accuracy -  +/-1° (20 to 180°, +/-1° (20 to 180°, 200 to 360°) 200 to 360°)
Resolution -  1° 1°
Frequency Range -  45 to 65 Hz.
Accuracy -  +/-0.1 Hz. (3 cycles minimum)
Resolution -  0.1 Hz.
Time - Events (<1sec): Hot to Neutral Neutral to Ground
Accuracy - +/-0.5 cycle +/-1 cycle
Resolution -  0.5 cycle 1 cycle
Time-stamp -
Accuracy -  +/-2 sec./day + resolution
Resolution -  8 seconds

PRODUCT SPECIFICATION FOR 220/240V

Memory Size- 4,000 events.
Common Specifications - See page 30.
Software Specifications - See page 39.
Surge, Sag & Outage - Hot to Neutral Neutral to Ground
Range - 0 to 400 V rms 0 to 50 V rms
Accuracy - +/-2 V rms +/-.25 V rms + resolution + resolution
Resolution -  2 V rms .25 V rms
Impulse - Hot to Neutral Neutral to Ground
Range - 100 to 2500 V peak 50 to 2500 V peak
Accuracy - +/-10% of reading +/-10% of reading + resolution + resolution
Resolution - 10 V 10 V Hot to Neutral Neutral to Ground
Width Detection: 1 µsec minimum 1 µsec minimum
Phase Angle -Accuracy: +/-1° (20 to 180°, +/-1° 20 to 180°, 200 to 360°) 200 to 360°)
Resolution - 1° 1° Frequency
Range - 45 to 65 Hz.
Accuracy -  +/-0.1 Hz. (3 cycles minimum)
Resolution: 0.1 Hz.
Time - Events (<1sec):Hot to Neutral Neutral to Ground
Accuracy - +/-0.5 cycle +/-1 cycle
Resolution - 0.5 cycle 1 cycle Time-stamp (Events > 1 second):
Accuracy -  +/-2 sec./day + resolution
Resolution - 8 seconds